Flushing Fails to Cool Drinking Water in Summer Heat, SBZ Online Reports

Drinking-water systems in German buildings can no longer rely on flushing alone to keep cold water below the 25 °C hygiene threshold, SBZ Online reported.

Summer heat has pushed mains-entry temperatures so high that even continuous flushing fails to cool pipes, while drought limits the water available for that flushing. “The flushing for temperature maintenance of cold drinking water thus fulfills neither the goal of avoiding water waste nor the assurance of hygiene through intended operation,” the report says.

DIN 1988-200 section 3.2.2 requires planners to avoid water waste and ensure sufficient water exchange during normal use. Yet the rules are fragmented: DIN EN 806-5 allows seven days between exchanges, VDI 6023 Part 1 recommends 72 hours, and some engineers argue for 24-hour cycles depending on water quality, materials and temperature, according to Sbz Online.

A comparison by Fachbereich Energie-Gebäude-Umwelt showed the impact of layout.

Conventional T-piece or series installations kept cold water above 25 °C for 14 hours a day and below 20 °C for only two hours. A ring-main design with flow dividers held the temperature under 20 °C for nearly 17 hours.

Active cooling is gaining traction. With active cooling – e.g. the system CoolFlow – a temperature in the circulating system of permanently ≤ 20 °C is possible, which reduces microbial growth.

“A responsible approach to drinking water means: every liter that does not flow away unused or is wasted for non-potable purposes is a step in the right direction,” the report concludes. The circulation of warm drinking water is a proven measure to improve hygienic conditions – the circulation with cooling in cold drinking water is the consequent and logical further development to make hygiene in PWC future-proof.